Wind Load Report - New Residence

1. Site & Building Data

Roof Type: Gable  
Wind Speed (ult): 110 mph
Exposure Category: C  
Enclosure Class: Enclosed  
Building Width (W): 76 ft.
Building Length (L): 90 ft.
Eave Height (he): 12 ft.
Foundation Height (hf): 0 ft.
Roof Pitch: 4 /12
Eave Overhang (OHe): 2 ft.
Gable Overhang (OHg): 2 ft.

2. Parameters & Coefficients

Topographic Factor (Kzt): 1.0
Directionality Factor (Kd): .85
Roof Angle (θ): 18.43 deg.
Mean Roof Height (h): 18.33 ft.
Ridge Height (hr): 24.67 ft.
Pos. Internal Pressure (+GCpi): +0.18  
Neg. Internal Pressure (-GCpi): -0.18  
Velocity Pressure Exp. Coeff. (Kh): 0.89 @ z=h
Velocity Pressure (qh): 23.32 psf
End Zone Width (a): 7.33 ft.
Zone 2/2E Dist.: 30.00 ft.

3. Design Assumptions and Notes

Code Standard: ASCE 7-10
Geometry: Regular-Shaped Bldg.
Height Class: Low-Rise Building
Notes:

4. Design Loads

Top Chord Dead Load: 7 psf
Bottom Chord Dead Load: 10 psf
Truss/Rafter Spacing: 24 in. o/c

4. Design Wind Pressures: MWFRS Envelope Procedure


Load Case A: Transverse Direction
Surface GCpf Design Pressure (psf)
(w/ +GCpi) (w/ -GCpi)
1 0.52 7.84 16.24
2 -0.69 -20.28 -11.89
3 -0.47 -15.12 -6.73
4 -0.42 -13.88 -5.49
1E 0.78 13.99 22.39
2E -1.07 -29.14 -20.75
3E -0.67 -19.90 -11.50
4E -0.62 -18.61 -10.21
2OH -0.69 -16.09
2EOH -1.07 -24.95
3OH -0.47 -10.92
3EOH -0.67 -15.70
2OH+W -0.69/-0.7 -31.73
2EOH+W -1.07/-0.7 -40.59
a) (+) and (-) signs signify wind pressures acting toward & away from surfaces.
b) External Pressure Coefficients linearly interpolated from Fig. 28.4-1 ASCE 7-10.
c) Design building for all wind directions, 4 load patterns per load case.
d) Total horizontal shear shall not be less than that by neglecting roof wind forces.
e) Min. wind load for enclosed or partially enclosed bldg.: 16 psf wall, 8 psf roof.
f) Design pressures are for strength design, multiply by 0.6 for ASD.
Wind Loads 3800 Harris Road Bakersfield 40728
Engineer Name ENGINEERING COMPANY INC.
Street Address City, CA 99999
ph. (800) 000-0000    www.website.com
-
7/28/2024 1
Subject
Customer
Location
Job No.
Engr.
Rev.
Date
Page

Load Case B: Longitudinal Direction
Surface GCpf Design Pressure (psf)
(w/ +GCpi) (w/ -GCpi)
1 -0.45 -14.69 -6.30
2 -0.69 -20.28 -11.89
3 -0.37 -12.82 -4.43
4 -0.45 -14.69 -6.30
5 0.40 5.13 13.52
6 -0.29 -10.96 -2.56
1E -0.48 -15.39 -6.99
2E -1.07 -29.14 -20.75
3E -0.53 -16.55 -8.16
4E -0.48 -15.39 -6.99
5E 0.61 10.03 18.42
6E -0.43 -14.22 -5.83
2OH -0.69 -16.09
2EOH -1.07 -24.95
3OH -0.37 -8.63
3EOH -0.53 -12.36
2EOH+W -1.07/-0.7 -41.27
3EOH+W -0.53/-0.7 -28.68
a) (+) and (-) signs signify wind pressures acting toward & away from surfaces.
b) External Pressure Coefficients linearly interpolated from Fig. 28.4-1 ASCE 7-10.
c) Design building for all wind directions, 4 load patterns per load case.
d) Total horizontal shear shall not be less than that by neglecting roof wind forces.
e) Min. wind load for enclosed or partially enclosed bldg.: 16 psf wall, 8 psf roof.
f) Design pressures are for strength design, multiply by 0.6 for ASD.


Torsional Load Cases
Surface Load Case GCpf Design Pressure (psf)
(w/ +GCpi) (w/ -GCpi)
1T A - 1.96 4.06
2T A - -5.07 -2.97
3T A - -3.78 -1.68
4T A - -3.47 -1.37
5T B - 1.28 3.38
6T B - -2.74 -0.64
a) (+) and (-) signs signify wind pressures acting toward & away from surfaces.
b) Pressures designated with a "T" are 25% of full design wind pressures.
c) Torsional loading shall apply to all 8 load patterns using the figures shown.
d) Design pressures are for strength design, multiply by 0.6 for ASD.
e) Torsional Design Exceptions: One story bldg. with h ≤ 30 ft,
   Two stories or less framed with light frame construction,
   Two stories or less with flexible diaphragms.
Wind Loads 3800 Harris Road Bakersfield 40728
Engineer Name ENGINEERING COMPANY INC.
Street Address City, CA 99999
ph. (800) 000-0000    www.website.com
-
7/28/2024 2
Subject
Customer
Location
Job No.
Engr.
Rev.
Date
Page

5. Wind Load Calculations


1.) Lateral Loads - Transverse Direction:


Lateral Loads on Roof Diaphragm with Positive Internal Pressure
90 ft.
14.67 ft.
75.33 ft.
67.0 plf
50.0 plf
50.4 plf
28.2 plf
1795 lbs
1688 lbs
151.2 plf
114.9 plf
31.8 plf
24.2 plf
174.9 plf
121.7 plf
149.7 plf
96.5 plf
16.2 plf
12.7 plf
25.1 plf
17.5 plf
119.3 plf
83.0 plf
6.3 plf
4.4 plf
2 ft.
2 ft.
a) (-) signs signify wind lateral forces acting opposite to the direction of the arrows shown.
b) Strength design values multiplied by 0.6 to obtain ASD values.



Wind Base Shear (ASD)
Load Case A: Transverse Direction
Load Case Walls (lbs) Roof (lbs) Roof Overhangs (lbs) Total Lateral Load (lbs) R1 (lbs) R2 (lbs)
Positive Internal Pressure 7613 -3148 -983 3483 1795 1688
Negative Internal Pressure 7613 -3148 -983 3483 1795 1688
Roof Pressure = 0 7613 0 0 7613 4047 3566
Min. Pressures (8 psf, 16 psf) 5184 5472 544 11200 5600 5600
a) Bottom half of wall neglected in tributary area calculations.
b) Strength design values multiplied by 0.6 to obtain ASD values.
Wind Loads 3800 Harris Road Bakersfield 40728
Engineer Name ENGINEERING COMPANY INC.
Street Address City, CA 99999
ph. (800) 000-0000    www.website.com
-
7/28/2024 3
Subject
Customer
Location
Job No.
Engr.
Rev.
Date
Page

2.) Lateral Loads - Longitudinal Direction:


Lateral Loads on Roof Diaphragm with Positive Internal Pressure
76 ft.
7.33 ft.
68.67 ft.
51.2 plf
39.4 plf
36.1 plf
18.5 plf
130.4 lbs
723.6 lbs
1512.9 lbs
2323.0 lbs
4770 lbs
4537 lbs
a) (-) signs signify wind lateral forces acting opposite to the direction of the arrows shown.
b) Strength design values multiplied by 0.6 to obtain ASD values.
c) Where the length of building (L) exceeds 4X the mean roof height (h), wind drag forces should additionally be considered.



Wind Base Shear (ASD)
Load Case B: Longitudinal Direction
Load Case Walls (lbs) Gable Ends (lbs) Roof (lbs) Total Lateral Load (lbs) RA (lbs) RB (lbs)
Positive Internal Pressure 4617 4690 0 9307 4770 4537
Negative Internal Pressure 4617 4690 0 9307 4770 4537
Roof Pressure = 0 4617 4690 0 9307 4770 4537
Min. Pressures (8 psf, 16 psf) 4378 4621 0 8998 4499 4499
a) Bottom half of wall neglected in tributary area calculations.
b) Strength design values multiplied by 0.6 to obtain ASD values.
Wind Loads 3800 Harris Road Bakersfield 40728
Engineer Name ENGINEERING COMPANY INC.
Street Address City, CA 99999
ph. (800) 000-0000    www.website.com
-
7/28/2024 4
Subject
Customer
Location
Job No.
Engr.
Rev.
Date
Page

3.) Roof Truss Reactions:


Roof Truss/Rafter Reactions: Transverse End Zone
462 lbs
200 lbs
Max. Horz. ① = 201 lbs
Max. Uplift ① = 462 lbs
a) Strength design values multiplied by 0.6 to obtain ASD values.
b) Windward loads may be positive or negative depending on pitch of roof.



Roof Truss/Rafter Reactions (ASD)
w/ Positive Internal Pressure
Load Case Horizontal Load (lbs) Gross Uplift (lbs) Net Uplift (lbs) U1 (lbs) U2 (lbs)
Transverse Int. Zone 79 1667 47 105 -58
Transverse End Zone 131 2282 662 462 200
Longitudinal Int. Zone 119 1569 -51 69 -120
Longitudinal End Zone 201 2173 553 436 117
a) Gross Uplift calculations do not include any counteracting roof dead loads.
b) Net Uplift calculations include counteracting roof dead loads multiplied by 0.6 per load case (7) ASCE 7-10.
c) Strength design values multiplied by 0.6 to obtain ASD values for wind loads.
d) Loads based on truss spacing calculated at 24" o/c.
e) Negative values for horizontal load indicate load acting in windward direction (tranverse load cases).
f) Negative values for uplift indicate net downward force (zero uplift).













*Disclaimer: The calculations produced herein are for initial design and estimating purposes only. The calculations and drawings presented do not constitute a fully engineered design. All of the potential load cases required to fully design an actual structure may not be provided by this calculator. For the design of an actual structure, a registered and licensed professional should be consulted as per IRC 2012 Sec. R802.10.2 and designed according to the minimum requirements of ASCE 7-10. The wind load calculations provided by this online tool are for educational and illustrative purposes only. Medeek Design assumes no liability or loss for any designs presented and does not guarantee fitness for use.
Wind Loads 3800 Harris Road Bakersfield 40728
Engineer Name ENGINEERING COMPANY INC.
Street Address City, CA 99999
ph. (800) 000-0000    www.website.com
-
7/28/2024 5