1. Site & Building Data

Roof Type: Gable  
Wind Speed (ult): 110 mph
Exposure Category: C  
Enclosure Class: Enclosed  
Building Width (W): 108 ft.
Building Length (L): 167 ft.
Eave Height (he): 11.5 ft.
Foundation Height (hf): 0 ft.
Roof Pitch: 4 /12
Eave Overhang (OHe): 1.5 ft.
Gable Overhang (OHg): 1.5 ft.

2. Parameters & Coefficients

Topographic Factor (Kzt): 1.0
Directionality Factor (Kd): .85
Roof Angle (θ): 18.43 deg.
Mean Roof Height (h): 20.50 ft.
Ridge Height (hr): 29.50 ft.
Pos. Internal Pressure (+GCpi): +0.18  
Neg. Internal Pressure (-GCpi): -0.18  
Velocity Pressure Exp. Coeff. (Kh): 0.91 @ z=h
Velocity Pressure (qh): 23.87 psf
End Zone Width (a): 8.20 ft.
Zone 2/2E Dist.: 28.75 ft.

3. Design Assumptions and Notes

Code Standard: ASCE 7-10
Geometry: Regular-Shaped Bldg.
Height Class: Low-Rise Building
Notes:

4. Design Loads

Top Chord Dead Load: 7 psf
Bottom Chord Dead Load: 10 psf
Truss/Rafter Spacing: 24 in. o/c

4. Design Wind Pressures: MWFRS Envelope Procedure


Load Case A: Transverse Direction
Surface GCpf Design Pressure (psf)
(w/ +GCpi) (w/ -GCpi)
1 0.52 8.03 16.62
2 -0.69 -20.77 -12.17
3 -0.47 -15.48 -6.89
4 -0.42 -14.21 -5.62
1E 0.78 14.33 22.92
2E -1.07 -29.84 -21.24
3E -0.67 -20.37 -11.78
4E -0.62 -19.05 -10.46
2OH -0.69 -16.47
2EOH -1.07 -25.54
3OH -0.47 -11.18
3EOH -0.67 -16.07
2OH+W -0.69/-0.7 -32.12
2EOH+W -1.07/-0.7 -41.19
a) (+) and (-) signs signify wind pressures acting toward & away from surfaces.
b) External Pressure Coefficients linearly interpolated from Fig. 28.4-1 ASCE 7-10.
c) Design building for all wind directions, 4 load patterns per load case.
d) Total horizontal shear shall not be less than that by neglecting roof wind forces.
e) Min. wind load for enclosed or partially enclosed bldg.: 16 psf wall, 8 psf roof.
f) Design pressures are for strength design, multiply by 0.6 for ASD.
Wind Loads 6649 Rollin Brown Ct 40715
Engineer Name ENGINEERING COMPANY INC.
Street Address City, CA 99999
ph. (800) 000-0000    www.website.com
-
7/16/2024 1
Subject
Customer
Location
Job No.
Engr.
Rev.
Date
Page

Load Case B: Longitudinal Direction
Surface GCpf Design Pressure (psf)
(w/ +GCpi) (w/ -GCpi)
1 -0.45 -15.04 -6.44
2 -0.69 -20.77 -12.17
3 -0.37 -13.13 -4.54
4 -0.45 -15.04 -6.44
5 0.40 5.25 13.84
6 -0.29 -11.22 -2.63
1E -0.48 -15.75 -7.16
2E -1.07 -29.84 -21.24
3E -0.53 -16.95 -8.35
4E -0.48 -15.75 -7.16
5E 0.61 10.26 18.86
6E -0.43 -14.56 -5.97
2OH -0.69 -16.47
2EOH -1.07 -25.54
3OH -0.37 -8.83
3EOH -0.53 -12.65
2EOH+W -1.07/-0.7 -42.25
3EOH+W -0.53/-0.7 -29.36
a) (+) and (-) signs signify wind pressures acting toward & away from surfaces.
b) External Pressure Coefficients linearly interpolated from Fig. 28.4-1 ASCE 7-10.
c) Design building for all wind directions, 4 load patterns per load case.
d) Total horizontal shear shall not be less than that by neglecting roof wind forces.
e) Min. wind load for enclosed or partially enclosed bldg.: 16 psf wall, 8 psf roof.
f) Design pressures are for strength design, multiply by 0.6 for ASD.


Torsional Load Cases
Surface Load Case GCpf Design Pressure (psf)
(w/ +GCpi) (w/ -GCpi)
1T A - 2.01 4.16
2T A - -5.19 -3.04
3T A - -3.87 -1.72
4T A - -3.55 -1.40
5T B - 1.31 3.46
6T B - -2.80 -0.66
a) (+) and (-) signs signify wind pressures acting toward & away from surfaces.
b) Pressures designated with a "T" are 25% of full design wind pressures.
c) Torsional loading shall apply to all 8 load patterns using the figures shown.
d) Design pressures are for strength design, multiply by 0.6 for ASD.
e) Torsional Design Exceptions: One story bldg. with h ≤ 30 ft,
   Two stories or less framed with light frame construction,
   Two stories or less with flexible diaphragms.
Wind Loads 6649 Rollin Brown Ct 40715
Engineer Name ENGINEERING COMPANY INC.
Street Address City, CA 99999
ph. (800) 000-0000    www.website.com
-
7/16/2024 2
Subject
Customer
Location
Job No.
Engr.
Rev.
Date
Page

5. Wind Load Calculations


1.) Lateral Loads - Transverse Direction:


Lateral Loads on Roof Diaphragm with Positive Internal Pressure
167 ft.
16.40 ft.
150.60 ft.
65.7 plf
49.0 plf
49.4 plf
27.7 plf
3456 lbs
3301 lbs
220.0 plf
167.2 plf
102.9 plf
78.2 plf
171.6 plf
119.4 plf
146.9 plf
94.7 plf
12.4 plf
9.6 plf
81.2 plf
56.5 plf
173.6 plf
120.8 plf
4.8 plf
3.4 plf
1.5 ft.
1.5 ft.
a) (-) signs signify wind lateral forces acting opposite to the direction of the arrows shown.
b) Strength design values multiplied by 0.6 to obtain ASD values.



Wind Base Shear (ASD)
Load Case A: Transverse Direction
Load Case Walls (lbs) Roof (lbs) Roof Overhangs (lbs) Total Lateral Load (lbs) R1 (lbs) R2 (lbs)
Positive Internal Pressure 13445 -5471 -1217 6757 3456 3301
Negative Internal Pressure 13445 -5471 -1217 6757 3456 3301
Roof Pressure = 0 13445 0 0 13445 7007 6439
Min. Pressures (8 psf, 16 psf) 9218 14429 667 24314 12157 12157
a) Bottom half of wall neglected in tributary area calculations.
b) Strength design values multiplied by 0.6 to obtain ASD values.
Wind Loads 6649 Rollin Brown Ct 40715
Engineer Name ENGINEERING COMPANY INC.
Street Address City, CA 99999
ph. (800) 000-0000    www.website.com
-
7/16/2024 3
Subject
Customer
Location
Job No.
Engr.
Rev.
Date
Page

2.) Lateral Loads - Longitudinal Direction:


Lateral Loads on Roof Diaphragm with Positive Internal Pressure
108 ft.
8.20 ft.
99.80 ft.
50.2 plf
38.7 plf
35.4 plf
18.1 plf
166.9 lbs
1237.1 lbs
3454.9 lbs
4802.7 lbs
8152 lbs
7883 lbs
a) (-) signs signify wind lateral forces acting opposite to the direction of the arrows shown.
b) Strength design values multiplied by 0.6 to obtain ASD values.
c) Where the length of building (L) exceeds 4X the mean roof height (h), wind drag forces should additionally be considered.



Wind Base Shear (ASD)
Load Case B: Longitudinal Direction
Load Case Walls (lbs) Gable Ends (lbs) Roof (lbs) Total Lateral Load (lbs) RA (lbs) RB (lbs)
Positive Internal Pressure 6373 9662 0 16035 8152 7883
Negative Internal Pressure 6373 9662 0 16035 8152 7883
Roof Pressure = 0 6373 9662 0 16035 8152 7883
Min. Pressures (8 psf, 16 psf) 5962 9331 0 15293 7646 7646
a) Bottom half of wall neglected in tributary area calculations.
b) Strength design values multiplied by 0.6 to obtain ASD values.
Wind Loads 6649 Rollin Brown Ct 40715
Engineer Name ENGINEERING COMPANY INC.
Street Address City, CA 99999
ph. (800) 000-0000    www.website.com
-
7/16/2024 4
Subject
Customer
Location
Job No.
Engr.
Rev.
Date
Page

3.) Roof Truss Reactions:


Roof Truss/Rafter Reactions: Transverse End Zone
538 lbs
253 lbs
Max. Horz. ① = 286 lbs
Max. Uplift ① = 631 lbs
a) Strength design values multiplied by 0.6 to obtain ASD values.
b) Windward loads may be positive or negative depending on pitch of roof.



Roof Truss/Rafter Reactions (ASD)
w/ Positive Internal Pressure
Load Case Horizontal Load (lbs) Gross Uplift (lbs) Net Uplift (lbs) U1 (lbs) U2 (lbs)
Transverse Int. Zone 73 2267 -12 80 -92
Transverse End Zone 124 3070 791 538 253
Longitudinal Int. Zone 170 2242 -37 112 -149
Longitudinal End Zone 286 3100 822 631 190
a) Gross Uplift calculations do not include any counteracting roof dead loads.
b) Net Uplift calculations include counteracting roof dead loads multiplied by 0.6 per load case (7) ASCE 7-10.
c) Strength design values multiplied by 0.6 to obtain ASD values for wind loads.
d) Loads based on truss spacing calculated at 24" o/c.
e) Negative values for horizontal load indicate load acting in windward direction (tranverse load cases).
f) Negative values for uplift indicate net downward force (zero uplift).













*Disclaimer: The calculations produced herein are for initial design and estimating purposes only. The calculations and drawings presented do not constitute a fully engineered design. All of the potential load cases required to fully design an actual structure may not be provided by this calculator. For the design of an actual structure, a registered and licensed professional should be consulted as per IRC 2012 Sec. R802.10.2 and designed according to the minimum requirements of ASCE 7-10. The wind load calculations provided by this online tool are for educational and illustrative purposes only. Medeek Design assumes no liability or loss for any designs presented and does not guarantee fitness for use.
Wind Loads 6649 Rollin Brown Ct 40715
Engineer Name ENGINEERING COMPANY INC.
Street Address City, CA 99999
ph. (800) 000-0000    www.website.com
-
7/16/2024 5